Many people are afraid that after they buy our CDCS guide torrent they may fail in the exam and the refund procedure will be very complicated. We guarantee to you that the refund process is very simple and only if you provide us the screenshot or the scanning copy of your failure marks we will refund you in full immediately. If you have doubts or problems about our CDCS Exam Torrent, please contact our online customer service or contact us by mails and we will reply and solve your problem as quickly as we can. We won’t waste your money and your time and if you fail in the exam we will refund you in full immediately at one time. We provide the best CDCS questions torrent to you and don’t hope to let you feel disappointed.
EXIN CDCS Exam Syllabus Topics:
Topic | Details |
---|---|
Topic 1 |
|
Topic 2 |
|
Topic 3 |
|
Free PDF 2025 EXIN Newest CDCS: EXIN EPI Certified Data Centre Specialist Discount Code
Our company conducts our CDCS real questions as high quality rather than unprincipled company which just cuts and pastes content into their materials and sells them to exam candidates. We have always been the vanguard of this field over ten years. It means we hold the position of supremacy of CDCS practice materials by high quality and high accuracy. Besides, all exam candidates who choose our CDCS real questions gain unforeseen success in this exam, and continue buying our CDCS practice materials when they have other exam materials’ needs. It is our running tenet to offer the most considerate help and services for exam candidates just like you. By virtue of our CDCS Study Tool, many customers get comfortable experiences of whole package of services and of course passing the CDCS exam successfully. Just hold the supposition that you may fail the exam even by the help of our CDCS study tool, we can give full refund back or switch other versions for you to relieve you of any kind of losses. What is more, we offer supplementary content like updates for one year after your purchase.
EXIN EPI Certified Data Centre Specialist Sample Questions (Q46-Q51):
NEW QUESTION # 46
You are working on the design of a new facility. The electrical riser of the building with high current power is located close to the area where sensitive IT equipment in the computer room will be located.
What should you recommend to reduce the amount of EMF coming from the electrical riser?
- A. Install bus bar trunking
- B. Install single-phase power cabling
- C. Install three-phase power cabling based on a combined cable (e.g. XLPE etc.)
- D. Install three-phase power cabling based on three individual core wires
Answer: C
Explanation:
To reduce Electromagnetic Fields (EMF) emanating from the electrical riser near sensitive IT equipment, three-phase power cabling in a combined cable (such as XLPE) is effective. Combined cabling helps reduce EMF by keeping the conductors tightly packed, which minimizes magnetic fields generated by current flow. Cables like XLPE (cross-linked polyethylene) also offer better insulation, which helps mitigate EMF interference with nearby IT equipment.
Detailed Explanation:
Using a combined three-phase cable reduces EMF because the magnetic fields generated by each phase tend to cancel each other out when in close proximity. This arrangement helps reduce the overall magnetic field strength. In addition, XLPE and similar materials provide good insulation, making them a preferred choice for reducing EMF emissions around sensitive equipment.
EPI Data Center Specialist References:
EPI data center best practices recommend mitigating EMF interference through combined cabling arrangements, especially near areas where sensitive IT equipment is located. Reducing EMF is crucial to maintaining equipment reliability and ensuring compliance with safety standards.
NEW QUESTION # 47
The electrical diagram of the data center shows the following UPS configuration and has a load of 80 kW.
What is the set-up in this data center?
- A. 2+N+1
- B. (N+1)-(N+1)
- C. N+N(+1)
- D. 2(N+1)
Answer: D
Explanation:
A 2(N+1) configuration implies two independent UPS systems, each with N+1 redundancy. This configuration provides high availability by ensuring that each UPS system can independently support the load with an additional unit for redundancy. Given the 80 kW load, this setup implies that two separate N+1 systems are running, providing reliability and fault tolerance for the data center's power needs.
Detailed Explanation:
The N+1 notation denotes that each system has one additional unit beyond what is needed to carry the load, providing redundancy. With 2(N+1), there are two such setups, ensuring that if one fails, the other can still support the load without interruption, fulfilling high availability requirements.
EPI Data Center Specialist References:
EPI teaches that multiple redundant systems, such as 2(N+1), enhance data center reliability by ensuring that power is maintained even if a failure occurs in one system. This meets the stringent demands for uptime in critical environments.
NEW QUESTION # 48
The UPS of a data center, with an ANSI/TIA-942 Rating-4, is installed with the rectifier connected to power feed A and the bypass/reserve line input connected to power feed B.
To which feed will the output of the UPS be synchronized?
- A. Feed B
- B. Depends on the setting of the UPS, as the UPS can normally be set to either feed
- C. The UPS will not synchronize to any of the feeds but use an internal clock to set the output voltage and frequency
- D. Feed A
Answer: B
Explanation:
For a UPS system in a Rating-4 data center, the synchronization of output can indeed depend on the specific settings of the UPS. Generally, such systems allow for flexible configuration where the output can be synchronized to either power feed A or B, depending on which feed is preferred for stability or redundancy purposes.
Detailed Explanation:
In dual-feed setups, such as those in high-redundancy data centers, the UPS can be set to synchronize with either feed. This ensures that the UPS maintains continuity in case one feed becomes unstable or fails. The flexibility to choose synchronization to either feed enhances the resiliency and reliability of power supply, which is critical in Tier IV (Rating-4) facilities where uptime is paramount.
EPI Data Center Specialist References:
The EPI Data Center Specialist course underscores the importance of configurable UPS systems in Rating-4 data centers, where redundancy and continuous power are critical. By allowing synchronization to either feed, the UPS can maintain the highest level of reliability, which aligns with the rigorous standards expected in such environments.
NEW QUESTION # 49
You are changing the design of the fire suppression system for your computer room from a halocarbon fire suppression system into an inert-based fire suppression system. Could you use the same formula to calculate the gas content for the gas?
- A. Yes, as long as you change the 'S' factor of the formula to reflect the gas type used.
- B. Yes, as long as you take the difference between the net and gross volume into account.
- C. No, there is a significant difference in the formula for the different types of fire suppression gases.
- D. Yes, as long as you use the same units of measure, i.e., kg/m³ or lbs/ft³.
Answer: C
Explanation:
The formula used to calculate the gas content differs significantly between halocarbon and inert-based fire suppression systems. Halocarbon systems function by absorbing heat, while inert systems work by reducing oxygen levels. Due to these differences in fire suppression mechanisms, distinct formulas are applied, factoring in the specific properties of each gas type and the required concentration levels.
Detailed Explanation:
Halocarbon systems like FM200 require a formula that accounts for the concentration needed for cooling, while inert gases like nitrogen or argon need a formula that calculates the volume based on oxygen displacement. As the design concentration and characteristics of these gases differ, it's essential to use the correct formula specific to the gas type.
EPI Data Center Specialist References:
EPI recommends consulting the specific design requirements and formulas provided by each gas manufacturer when switching fire suppression systems to ensure the correct amount of gas is deployed for effective fire suppression.
NEW QUESTION # 50
A new network storage device in a non-standard size rack of approximately 600 kg/1,300 lbs is going to be installed in the data center.
Are new floor loading calculations required?
- A. No, as long as the equipment is less than 700 kg/1,500 lbs it will be within the limits.
- B. No, specifications of equipment brought into the data center will already be known during the design of the data center, and therefore the floor will be able to handle it.
- C. Yes, a structural engineer, approved/endorsed by the building owner, should carry out new floor loading calculations.
- D. Yes, additional floor loading calculations need to be done by the floor manager, which should be verified by the safety engineer.
Answer: C
Explanation:
For heavy equipment, such as a network storage device weighing approximately 600 kg/1,300 lbs, new floor loading calculations are indeed required, particularly since the rack is non-standard. A structural engineer, approved by the building owner, should conduct these calculations to ensure the floor can safely support the new load without risking structural integrity.
Detailed Explanation:
Data centers are designed with specific floor load ratings, which are determined during the design phase based on anticipated equipment. When adding or replacing equipment that is significantly heavy or non-standard, reassessing the floor's capacity is essential to avoid overloading. A structural engineer has the expertise to verify if the existing floor can accommodate the weight and, if not, can recommend reinforcement measures.
This step ensures compliance with safety standards and helps prevent damage to the infrastructure, which could lead to costly repairs or even catastrophic failure in extreme cases.
EPI Data Center Specialist References:
EPI Data Center Specialist training advises that any changes in the data center load, particularly involving non-standard and heavy equipment, warrant a structural assessment. Ensuring compliance with floor load capacity is a critical safety and operational concern, as underscoring data center infrastructure reliability and safety is a priority in EPI's best practices.
NEW QUESTION # 51
......
Whether you are good at learning or not, passing the exam can be a very simple and enjoyable matter together with our CDCS practice engine. As a professional multinational company, we fully take into account the needs of each user when developing our CDCS Exam Braindumps. For example, in order to make every customer can purchase at ease, our CDCS preparation quiz will provide users with three different versions for free trial, corresponding to the three official versions.
CDCS Exam Review: https://www.validdumps.top/CDCS-exam-torrent.html
- www.dumps4pdf.com EXIN CDCS Desktop-based Practice Test Software 🪕 Search for ☀ CDCS ️☀️ on ✔ www.dumps4pdf.com ️✔️ immediately to obtain a free download ⬅New CDCS Dumps Ebook
- Updated CDCS Discount Code - High Hit Rate Source of CDCS Exam ⛽ Easily obtain free download of ➥ CDCS 🡄 by searching on ⇛ www.pdfvce.com ⇚ 😙CDCS Latest Exam Experience
- 100% Pass Efficient EXIN - CDCS - EXIN EPI Certified Data Centre Specialist Discount Code ➕ Download ➡ CDCS ️⬅️ for free by simply searching on ➡ www.torrentvce.com ️⬅️ 🙇New CDCS Dumps Ebook
- CDCS Study Material 🧊 CDCS Popular Exams 🏮 CDCS Test Torrent 💅 The page for free download of { CDCS } on ⮆ www.pdfvce.com ⮄ will open immediately 🛳CDCS Online Training Materials
- Free PDF Reliable EXIN - CDCS - EXIN EPI Certified Data Centre Specialist Discount Code 👕 Search for ➽ CDCS 🢪 on ( www.pass4leader.com ) immediately to obtain a free download 🚚CDCS Popular Exams
- EXIN CDCS study guide ♣ Search for { CDCS } and easily obtain a free download on ➽ www.pdfvce.com 🢪 🦲CDCS Popular Exams
- Helpful Features of EXIN CDCS PDF Questions 🐟 The page for free download of ➥ CDCS 🡄 on 《 www.prep4away.com 》 will open immediately 👷Online CDCS Test
- New CDCS Exam Topics 🐵 CDCS Test Torrent ▛ CDCS Best Vce 🏈 Search on ➽ www.pdfvce.com 🢪 for ☀ CDCS ️☀️ to obtain exam materials for free download 💌Valid CDCS Test Preparation
- CDCS Study Material 👾 Practice CDCS Exam 🪁 Test CDCS Cram Review 🥢 Search for 《 CDCS 》 and obtain a free download on { www.prep4away.com } 🐘Study CDCS Tool
- Free PDF Quiz Trustable EXIN - CDCS - EXIN EPI Certified Data Centre Specialist Discount Code 😦 Open ▷ www.pdfvce.com ◁ enter ⇛ CDCS ⇚ and obtain a free download 🍭CDCS Online Training Materials
- Free PDF Quiz Trustable EXIN - CDCS - EXIN EPI Certified Data Centre Specialist Discount Code ⏫ Immediately open ▛ www.exam4pdf.com ▟ and search for ☀ CDCS ️☀️ to obtain a free download 📹Online CDCS Test
- CDCS Exam Questions
- eishkul.com education.indiaprachar.com examstudy.pro vincead319.methblog.com sah-it.com studentsfavourite.com quorahub.org essarag.org www.zhen.net adamkin848.theblogfairy.com